Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T00CM02463
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/31/2000 | ELECTRIC - INTERMEDIATE | Correction Required | ADDTL COMMS - 1. DISCONNECT FOR WH NOT INSTALLED NO 30 A CD PER PLAN 2. RECEPTACLE TO BE RAISED BY SINK NOT IN 3. NEW SERVICE ADDRESSED 215 PERMIT SHOWS 216? 4. INSTALL REJECT PINS IN DISCONNECT FOR R TYPE FUSES 5. LB ENTERING METER ENCLOSURE CANNOT USE BROKEN FITTING TO CONNECT LB NEED TO USE A GROUND BUSHING AT SERVICE EQUIPMENT AROUND CONCENTRIC OR EXCENTRIC KOS 6. SUPPORT SEAL TIGHT PER 99 NEC WITHIN 12 OF ENCLOSURE |