Permit: T00CM02463

Parcel: 11005014C


Addresses:

2960 N SWAN RD #216


Inspection Status: Correction Required

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T00CM02463

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/31/2000 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - 1. DISCONNECT FOR WH NOT INSTALLED NO 30 A CD PER PLAN 2. RECEPTACLE TO BE RAISED BY SINK NOT IN 3. NEW SERVICE ADDRESSED 215 PERMIT SHOWS 216? 4. INSTALL REJECT PINS IN DISCONNECT FOR R TYPE FUSES 5. LB ENTERING METER ENCLOSURE CANNOT USE BROKEN FITTING TO CONNECT LB NEED TO USE A GROUND BUSHING AT SERVICE EQUIPMENT AROUND CONCENTRIC OR EXCENTRIC KOS 6. SUPPORT SEAL TIGHT PER 99 NEC WITHIN 12 OF ENCLOSURE