Permit: T00CM02332
Permit Details
Apply Date:
05/08/2000
Applicant:
FERGUSON RONALD D & SHERRI A CP/
Description:
VETERINARY CLINIC T99VL03063
Architects:
- HIGHTON, JULIE ANNE
Contractors:
- ARIZONA GENERAL ENGINEERING CONT
Permit Reviews
Permit Number - T00CM02332
Permit Status: C of o
Permit Description: VETERINARY CLINIC T99VL03063
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/31/2000 | REVISION | 10/31/2000 | COMPLETED |
Completed Inspections
Permit Status: C of o
Permit Number: T00CM02332
Permit Description: VETERINARY CLINIC T99VL03063
Total Completed Inspections - 9
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2000 | PLUMBING - SEWER HCS CONNECT | JSTANLEY | Approved | |
| 08/15/2000 | MECHANICAL - PROGRESS | CWILLIAM | Approved | IVRS - Inspection 0999* COPPER REFRIGERANT LINES IN CONTACT WITH STEEL STRAPING CONDENSATE DRAIN WILL NOT ACCEPT PRIMARY TERMINATING INTO SAN TEE IN WALL TERMINATE DOWN INTO SINK TAIL PIECE AS OUT WEST WALL OUTSIDE AIR INTAKE OSA IS THIS GOING TO BE PULLED FROM ATTIC SPACE? CHECK EXTENDED DUCT WRAP COMING LOOSE ON SOME LATTERAL RUNS CORRECT RECALL |
| 08/17/2000 | PLUMBING - ROUGH, SOIL | JSTANLEY | Approved | NEED APPROVED REVISED PLANS |
| 08/18/2000 | PLUMBING - ABOVE CEILING | JSTANLEY | Approved | PLEASE REMOVE SAN TEE 1 1/2" ABANDON FOR CONDENSATE LINE NEED APPROVED REVISED DRAWINGS NO SUPER ON JOB I WAS TOLD THAT I WOULD HAVE REVISED DRAWING BY NEXT INSPECTION |
| 08/21/2000 | PLUMBING - INTERMEDIATE | JSTANLEY | Approved | IVRS - Inspection 0000* PARTIAL OK PLEASE PROVIDE APPROVED REVISED PLAN SHOWING FLAT VENT ON W.C |
| 11/16/2000 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection 0000* OK TO CLEAR POWER NEED TO SEE X-RAY TABLE CONNECTION NOTES X-RAY TABLE TO HAVE A LISTING LABEL FROM AN APPROVED TESTING LABROTORY |
| 01/08/2001 | PERMIT FINALED | EMONAHAN | Approved | |
| 01/08/2001 | BUILDING - FINAL | EMONAHAN | Approved | IVRS - Inspection 0000* |
| 01/09/2001 | MECHANICAL - FINAL | CWILLIAM | Approved | IVRS - Inspection 0000* |