Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM02332
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/16/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK TO CLEAR POWER NEED TO SEE X-RAY TABLE CONNECTION NOTES X-RAY TABLE TO HAVE A LISTING LABEL FROM AN APPROVED TESTING LABROTORY |
|
| 11/15/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* WATER HEATER NOT INTENDED TO BE CORD CONNECTED 700-7 (A) (8) FILL UNUSED OPENINGS AT PANEL FILLER BLANK NEED TO SEE CONNECTION TO X-RAY TABLE |
|
| 10/26/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 10/26/00 NEED LIGHT FIXTURE FRONT PORCH LOOSE FITTING AT INSIDE DOSCONNECT AND STRAP CONDUIT NEED WIRE AND MAKE UP FOR DISCONNECT NEED EQUIPMENT ATTACHED AND HOOKED UP SEAL CONDUIT BODIES SEAL UNUSED HOLES IN PANEL INSTALL DEAD FRONT EXPOSED ROMEX NEED DISCONNECTING MEANS AND WATER HEATER INSTALLED NEED GFCI IN BATHROOM |
|
| 10/18/2000 | ELECTRIC - FINAL | Denied | 10/18/00 NO ACCESS LOCKED , RECALL |