Permit: T00CM02315
Permit Details
Status:
Expired
Type:
COMMERCIAL NEW
Address:
12855 W MILE WIDE RD
Address NEW:
12855 W MILE WIDE RD
Apply Date:
05/05/2000
Applicant:
CITY OF TUCSON
Description:
WELL SITE/FENCING/CONTROL BUILDING
Contractors:
- SUN WESTERN CONTRACTORS
Permit Reviews
Permit Number - T00CM02315
Permit Status: Expired
Permit Description: WELL SITE/FENCING/CONTROL BUILDING
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/30/2001 | REVISION | 02/13/2001 | COMPLETED |
Outstanding Inspections
Permit Status: Expired
Permit Number: T00CM02315
Permite Description: WELL SITE/FENCING/CONTROL BUILDING
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2001 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0935*1. BOND DISCONNECT ENCLOSURE 2. BOND GUTTER WITH FUSES 3. PLANS DO NOT SHOW SURGE ARRESTORS ON BREAKERS OR FUSES RATED HIGHER THAN CONDUCTOR CAPACITY/FUSE & BREAKERS ACCORDINGLY 4. TIGHTEN LOOSE SEALTIGHT CONNECTORS 5. BONDING DEVICE NEEDED AT CONCENTRIC KNOCKOUTS. |
Completed Inspections
Permit Status: Expired
Permit Number: T00CM02315
Permit Description: WELL SITE/FENCING/CONTROL BUILDING
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2000 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | OK TO COVER |
| 09/27/2000 | REINFORCED MASONRY PRE-GROUT | AMATHIES | Approved | IVRS - Inspection 0000* |
| 12/01/2000 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection 0000* OK UNDERGROUND 2-3' 6-3/4" |
| 02/23/2001 | ELECTRIC - TEMPORARY SERVICE | DSANTACR | Approved | IVRS - Inspection 0000* |
| 02/23/2001 | ELECTRIC - CABLE DROP | DSANTACR | Approved | IVRS - Inspection 0000* |