Permit: T00CM02315
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935*1. BOND DISCONNECT ENCLOSURE 2. BOND GUTTER WITH FUSES 3. PLANS DO NOT SHOW SURGE ARRESTORS ON BREAKERS OR FUSES RATED HIGHER THAN CONDUCTOR CAPACITY/FUSE & BREAKERS ACCORDINGLY 4. TIGHTEN LOOSE SEALTIGHT CONNECTORS 5. BONDING DEVICE NEEDED AT CONCENTRIC KNOCKOUTS. | |
| 04/03/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) NEED MANUFACTURERS INSTRUCTIONS PER NOTE ON PREVIOS INSP. 2) TIGHTEN ALL FITTINGS 3) NEED REVISED PLANS FOR THIS SITE |
|
| 03/13/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) TIGHTEN ALL LOOSE LUCKNUTS 2) IDENTIFY GROUNDING CONDUCTORS 3) TIGHTEN FITTINGS 4) SURGE ARESTOR-NEED MANUFACTURERS INSTRUCTIONS TO DETERMINE BREAKER SIZE TO CONDUCTORS (#14 WIRE ON 30AMP BREAKER) 5) WORKING CLEARANCES IN FRONT OF GUTTER WITH FUSES 6) FINISH CHLORENE INJECTOR STATION 7) NEED TO SEE REVISED PLANS FOR THIS SITE |