Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address NEW:
6235 E BROADWAY BL
Apply Date:
03/08/2000
Applicant:
METRO PERMIT EXPRESS
Description:
TI:OFFICE
Architects:
  • SWAN WAYNE E
Contractors:
  • FOOD SERVICE CONCEPTS INC ,

Completed Inspections

Permit Status: C of o
Permit Number: T00CM01135
Permit Description: TI:OFFICE
Total Completed Inspections - 5
Date Description Inspector Results Comments
03/28/2000 PLUMBING - ROUGH, SOIL TRINIVJR Approved ADDTL COMMS - 1. SOIL WATER TEST OK 2. WILL REQUIRE REVISED AND APPROVED DRAWING ON WASTE AND VENT IZO BEFORE FINAL 3. OK TO BACKFILL TRENCH
03/30/2000 ELECTRIC - UNDERGROUND KBOLLE Approved ADDTL COMMS - PLEASE NOTE PLAN CHECK AND ENGINEER FAILED TO NOTE THAT THIS CLINIC/MED FACILITY REQUIRES AN ELEC SYSTEM THAT COMPLIES WITH 517-13 IN ALL PATIENT CARE AREAS.
04/12/2000 PLUMBING - INTERMEDIATE TRINIVJR Approved ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. OK TO DRYWALL
04/19/2000 PLUMBING - ABOVE CEILING TRINIVJR Approved ADDTL COMMS - 1. OK FOR GRID
04/24/2000 MECHANICAL - INTERMEDIATE JMILITEL Approved ADDTL COMMS - 1. DUCT ABOVE HARD LID OK 2. MAY PROCEED WITH SHEET ROCK 3. NEED TO SEE APPROVED DRAWINGS FOR DATA AIRE UNIT IN SURGERY ROOM