Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T00CM01135
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2000 | ELECTRIC - UNDERGROUND | Correction Required | ADDTL COMMS - PLEASE NOTE PLAN CHECK AND ENGINEER FAILED TO NOTE THAT THIS CLINIC/MED FACILITY REQUIRES AN ELEC SYSTEM THAT COMPLIES WITH 517-13 IN ALL PATIENT CARE AREAS. |