Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T00CM01135
Permit Details
Apply Date:
03/08/2000
Applicant:
METRO PERMIT EXPRESS
Description:
TI:OFFICE
Architects:
- SWAN WAYNE E
Contractors:
- FOOD SERVICE CONCEPTS INC ,
Completed Inspections
Permit Status: C of o
Permit Number: T00CM01135
Permit Description: TI:OFFICE
Total Completed Inspections - 5
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/28/2000 | PLUMBING - ROUGH, SOIL | TRINIVJR | Approved | ADDTL COMMS - 1. SOIL WATER TEST OK 2. WILL REQUIRE REVISED AND APPROVED DRAWING ON WASTE AND VENT IZO BEFORE FINAL 3. OK TO BACKFILL TRENCH |
03/30/2000 | ELECTRIC - UNDERGROUND | KBOLLE | Approved | ADDTL COMMS - PLEASE NOTE PLAN CHECK AND ENGINEER FAILED TO NOTE THAT THIS CLINIC/MED FACILITY REQUIRES AN ELEC SYSTEM THAT COMPLIES WITH 517-13 IN ALL PATIENT CARE AREAS. |
04/12/2000 | PLUMBING - INTERMEDIATE | TRINIVJR | Approved | ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. OK TO DRYWALL |
04/19/2000 | PLUMBING - ABOVE CEILING | TRINIVJR | Approved | ADDTL COMMS - 1. OK FOR GRID |
04/24/2000 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | ADDTL COMMS - 1. DUCT ABOVE HARD LID OK 2. MAY PROCEED WITH SHEET ROCK 3. NEED TO SEE APPROVED DRAWINGS FOR DATA AIRE UNIT IN SURGERY ROOM |