Permit: T00CM01010
Permit Details
Apply Date:
03/01/2000
Applicant:
OUTPOST GROUP-LANTERRA
Description:
SFR:TD#14-62-03
Contractors:
- DOUCETTE HOMES INC
Completed Inspections
Permit Status: Final
Permit Number: T00CM01010
Permit Description: SFR:TD#14-62-03
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2000 | MECHANICAL - FINAL | JRIVA | Approved | IVRS - Inspection 0999* |
| 11/20/2000 | PLUMBING - FINAL | JRIVA | Approved | IVRS - Inspection 0999* |
| 11/20/2000 | ELECTRIC - FINAL | JRIVA | Approved | IVRS - Inspection 0999* |
| 11/20/2000 | BUILDING - FINAL | JRIVA | Approved | IVRS - Inspection 0999*/1. CLEAN OUT MUST BE TRIMMED TO GRADE AMP INSTALL APPROVED CAP. 2. HOSE BIBS NOT INSTALLED ALSO ANTI SIPHON BREAKERS. 3. CLEAN OUTS NOT CAPPED. 4. AC CONDENSER REQUIRES MAX 35 AMP FUSE/BREAKER. 5. INCORRECT WIRE ON IRRIGATION NEUTRAL. 6. MICROWAVE/KGFCI, S RU/WASHER, REFRIG/NOOK, DISHWASHER/DISPOSAL, BATH GFI/KITCH GFI ARE MULTI WIRE CIRCUITS COMPLY WITH 1999 NEC SECTION 210-4. 7. IRRIGATION CIRCUIT CANNOT PIGGY BACK ON LIGHT CIRCUIT BREAKER. 8. ELECTRIC SERVICE REQ NON WATER BOND LABLE. |
| 01/19/2001 | PERMIT FINALED | JRIVA | Approved | |
| 01/19/2001 | PLUMBING - YARD WTR LINE/TEST | JRIVA | Approved | IVRS - Inspection 0000* |