Permit: T00CM01010


Addresses:

3649 N SUNTERRA CT

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
01/19/2001 BUILDING - FINAL Approved IVRS - Inspection 0000*
11/20/2000 BUILDING - FINAL Denied IVRS - Inspection 0999*/1. CLEAN OUT MUST BE TRIMMED TO GRADE AMP INSTALL APPROVED CAP. 2. HOSE BIBS NOT INSTALLED ALSO ANTI SIPHON BREAKERS. 3. CLEAN OUTS NOT CAPPED. 4. AC CONDENSER REQUIRES MAX 35 AMP FUSE/BREAKER. 5. INCORRECT WIRE ON IRRIGATION NEUTRAL. 6. MICROWAVE/KGFCI, S RU/WASHER, REFRIG/NOOK, DISHWASHER/DISPOSAL, BATH GFI/KITCH GFI ARE MULTI WIRE CIRCUITS COMPLY WITH 1999 NEC SECTION 210-4. 7. IRRIGATION CIRCUIT CANNOT PIGGY BACK ON LIGHT CIRCUIT BREAKER. 8. ELECTRIC SERVICE REQ NON WATER BOND LABLE.