Status:
Expired
Type:
SINGLE FAMILY ALTERATION
Address NEW:
4541 E DOUGLAS ST
Apply Date:
01/27/2000
Applicant:
ALCAZAR HECTOR & HERNANDEZ ROSA
Description:
ENCLOSE:CARPORT TO ROOM T99VL02005

Outstanding Inspections

Permit Status: Expired
Permit Number: T00CM00383
Permite Description: ENCLOSE:CARPORT TO ROOM T99VL02005
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
02/18/2000 BUILDING - FINAL N/A Correction Required ADDTL COMMS - NOT READY - NEED SPANISH SPEAKING INSPECTOR. FINAL INSPECTION ONLY. BUILT WITHOUT PERMIT OR INSPECTION. 1. SERVICE PANEL IS IN A HAZARDOUS CONDITION. NEEDS TO BE REPLACED. 2. SUB-PANEL FEED FROM SERVICE TO NEW ADDITION. FED WITH #10 WIRE. DOUBLE FED AT SERVICE CIRCUIT. NOT PROTECTED. 3. CLEAN UP ALL WIRING INSIDE BUILDING. BOXES, ROMEX CONNECTORS ELECTRIC. REMOVE ALL DEAD CIRCUITS. 4. PLOT PLAN SHOWS BUILDING 5-0 FROM P.L. ON SITE INSPECTION SHOWS 2 TO P.L. AND APPROXIMATELY 4 TO CARPORT ON AJACENT LOT. NEED RATED WALL AND PLOT PLAN APPROVED. 5. NO NEUTRAL RUN FOR SERVICE FEED TO SUB-PANEL. 220 RUN TO SUB-PANEL. NEED 4 WIRES TO RUN BOTH 220 AND 110. 6. ISOLATE NEUTRALS FROM GROUND. INSTALL GROUND BUSS.