Permit: T00CM00383
Permit Details
Status:
Expired
Type:
SINGLE FAMILY ALTERATION
Address:
4541 E DOUGLAS ST
Address NEW:
4541 E DOUGLAS ST
Apply Date:
01/27/2000
Applicant:
ALCAZAR HECTOR & HERNANDEZ ROSA
Description:
ENCLOSE:CARPORT TO ROOM T99VL02005
Outstanding Inspections
Permit Status: Expired
Permit Number: T00CM00383
Permite Description: ENCLOSE:CARPORT TO ROOM T99VL02005
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2000 | BUILDING - FINAL | N/A | Correction Required | ADDTL COMMS - NOT READY - NEED SPANISH SPEAKING INSPECTOR. FINAL INSPECTION ONLY. BUILT WITHOUT PERMIT OR INSPECTION. 1. SERVICE PANEL IS IN A HAZARDOUS CONDITION. NEEDS TO BE REPLACED. 2. SUB-PANEL FEED FROM SERVICE TO NEW ADDITION. FED WITH #10 WIRE. DOUBLE FED AT SERVICE CIRCUIT. NOT PROTECTED. 3. CLEAN UP ALL WIRING INSIDE BUILDING. BOXES, ROMEX CONNECTORS ELECTRIC. REMOVE ALL DEAD CIRCUITS. 4. PLOT PLAN SHOWS BUILDING 5-0 FROM P.L. ON SITE INSPECTION SHOWS 2 TO P.L. AND APPROXIMATELY 4 TO CARPORT ON AJACENT LOT. NEED RATED WALL AND PLOT PLAN APPROVED. 5. NO NEUTRAL RUN FOR SERVICE FEED TO SUB-PANEL. 220 RUN TO SUB-PANEL. NEED 4 WIRES TO RUN BOTH 220 AND 110. 6. ISOLATE NEUTRALS FROM GROUND. INSTALL GROUND BUSS. |
| 02/18/2000 | ELECTRIC - FINAL | N/A | Not ready for Inspection | IVRS - Inspection 0000* |