Inspection Status: Correction Required
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/18/2000 |
BUILDING - FINAL |
|
Correction Required |
ADDTL COMMS - NOT READY - NEED SPANISH SPEAKING INSPECTOR. FINAL INSPECTION ONLY. BUILT WITHOUT PERMIT OR INSPECTION. 1. SERVICE PANEL IS IN A HAZARDOUS CONDITION. NEEDS TO BE REPLACED. 2. SUB-PANEL FEED FROM SERVICE TO NEW ADDITION. FED WITH #10 WIRE. DOUBLE FED AT SERVICE CIRCUIT. NOT PROTECTED. 3. CLEAN UP ALL WIRING INSIDE BUILDING. BOXES, ROMEX CONNECTORS ELECTRIC. REMOVE ALL DEAD CIRCUITS. 4. PLOT PLAN SHOWS BUILDING 5-0 FROM P.L. ON SITE INSPECTION SHOWS 2 TO P.L. AND APPROXIMATELY 4 TO CARPORT ON AJACENT LOT. NEED RATED WALL AND PLOT PLAN APPROVED. 5. NO NEUTRAL RUN FOR SERVICE FEED TO SUB-PANEL. 220 RUN TO SUB-PANEL. NEED 4 WIRES TO RUN BOTH 220 AND 110. 6. ISOLATE NEUTRALS FROM GROUND. INSTALL GROUND BUSS. |
| 02/18/2000 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |