Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
07/24/2000
Applicant:
KAUFMAN AND BROAD OF TUCSON ****
Description:
TEMP FBB:CONSTRUCTION TRAILER &ELECTRIC/SEWER
Contractors:
  • KAUFMAN AND BROAD OF TUCSON ****

Permit Reviews

Permit Number - T00BU02227
Permit Status: Expired
Permit Description: TEMP FBB:CONSTRUCTION TRAILER &ELECTRIC/SEWER
Start Date Submittal Complete Date Status  
07/24/2000 RESIDENTIAL BLDG/ZONING 07/25/2000 COMPLETED Review Details

Outstanding Inspections

Permit Status: Expired
Permit Number: T00BU02227
Permite Description: TEMP FBB:CONSTRUCTION TRAILER &ELECTRIC/SEWER
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
08/03/2000 ELECTRIC - FINAL N/A Partial Approval IVRS - Inspection 0000*
REPLACE MAIN BREAKER AT SUB PANEL WITH 100 AMP MAX
08/03/2000 PLUMBING - FINAL N/A Partial Approval IVRS - Inspection 0000*
1. NEED PRESSURE TEST ON POTABLE WATER LINE

Completed Inspections

Permit Status: Expired
Permit Number: T00BU02227
Permit Description: TEMP FBB:CONSTRUCTION TRAILER &ELECTRIC/SEWER
Total Completed Inspections - 2
Date Description Inspector Results Comments
08/03/2000 ELECTRIC - TEMPORARY SERVICE RSUBA Approved EXPOSE GROUND ROD RODS
EXPOSE CONDUIT BUSHING IN TRENCH
CONNECT THE GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO THE NEUTRAL BUS BAR NOT THE EQUIP, GROUNDING BUS BAR
PUT ADDRESS ON PEDASTAL PER TEP
CONNECT THE CONST TRAILER
08/03/2000 ELECTRIC - CABLE DROP RSUBA Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW