Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T00BU02227
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2000 | ELECTRIC - TEMPORARY SERVICE | Denied | EXPOSE GROUND ROD RODS EXPOSE CONDUIT BUSHING IN TRENCH CONNECT THE GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO THE NEUTRAL BUS BAR NOT THE EQUIP, GROUNDING BUS BAR PUT ADDRESS ON PEDASTAL PER TEP CONNECT THE CONST TRAILER |