Permit: SP-NRP-0426-00085
Permit Details
Apply Date:
04/29/2026
Applicant:
Brian Devlin
Description:
Electric service reconect
Outstanding Inspections
Permit Status: Inspections
Permit Number: SP-NRP-0426-00085
Permite Description: Electric service reconect
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2026 | Reconnect Only: Electrical Clearance | N/A | Re-inspection required | 5/5/26: New Roof top unit and new ductwork installed. RTU replaced swamp cooler ( electrical load calc required for added circuit,), open ceiling in hallways and rooms to verify proper ducting systems and supports, Manual-J required for new mechanical work. Electrical clearance cannot be sent until items above are addressed (home is vacant), smoke detectors missing throughout. |