Permit: TD-DEV-1223-00486

Parcel: 106070030


Addresses:

3300 N FAIRVIEW AV

Inspection Status: Not Applicable

Inspection History: For trash and recycling enclosures

Date Description Inspector Results Comments
02/18/2026 For trash and recycling enclosures Not Applicable Redundant inspection, not necessary.
02/18/2026 For trash and recycling enclosures Partial Pass Material storage yard at SW corner of park: footing dimensions and reinforcement are good, slab excavation dimensions and reinforcement (#4 12" OC both ways) are good. Okay to pour footing and slab.
03/16/2026 For trash and recycling enclosures Partial Pass 3/16/26 SW Material Enclosers-Reinforcing correct to top of walls. Grout all reinforced cells and including bond beams with vibrator.
08/26/2025 For trash and recycling enclosures Partial Pass East enclosure: bollards and reinforcement are good to pour slab, approach, and footing. Next inspection at 4 foot wall height, pre-grout.
08/26/2025 For trash and recycling enclosures Partial Pass West enclosure: bollards and reinforcement are good to pour slab, approach, and footing. Next inspection at 4 foot wall height, pre-grout.
09/04/2025 For trash and recycling enclosures Partial Pass Wall construction and reinforcement are good; okay to grout up to 4 feet. Call next inspection when wall is at 6 ft, before final grout.
09/04/2025 For trash and recycling enclosures Partial Pass West enclosure: Wall construction and reinforcement are good; okay to grout up to 4 feet. Call next inspection when wall is at 6 ft, before final grout.
09/09/2025 For trash and recycling enclosures Partial Pass Both enclosures: Wall construction and reinforcement are good; okay to grout to finish height.