Inspection Status: Partial Pass
Inspection History
| Date |
Description |
Inspector |
Results |
Comments |
| 09/16/2026 |
|
|
Partial Pass |
Send pictures of weep holes per detail before pouring. Reinforcing okay. Okay to pour pending pictures from contractor |
| 09/25/2026 |
|
|
Partial Pass |
Okay to backfill wall. Reschedule inspection for rock pockets at weep holes. |
| 10/01/2026 |
|
|
Partial Pass |
Retaining wall #6 okay to pour |
| 10/07/2026 |
|
|
Partial Pass |
Retaining wall#1 dimensions and reinforcing correct. Footer okay to pour. |
| 10/09/2026 |
|
|
Re-inspection required |
insufficient clearance to form. Chair back face prior to reinspection. Appears to be missing 2’ H=3-04 step at STA 0+00. Many verticals require trimming or splicing. Maintain 2” clearance and cover. splices are not staggered - splices shall be staggered no less than 1 splices length. 3/4” chamfer missing from top of form. Modify bottom of form to provide clearance to bent dowels. |
| 10/13/2026 |
|
|
Not Ready |
10/13/26 Reinforcing, weep holes, laps and layout is good but not complete. Spacing of rebar relative to forms needs to be complete. Reschedule inspection when ready. |
| 10/14/2026 |
|
|
Partial Pass |
Issues in history have been addressed. Okay to pour pending pictures showing areas discussed with contractor.. |
| 10/15/2026 |
|
|
Partial Pass |
1st Footer wall 5 at placida and Santiago ok to pour. |
| 10/21/2026 |
|
|
Partial Pass |
Wall #5 Okay to pour. |
| 10/27/2026 |
|
|
Partial Pass |
Wall waterproofed and backfill occurring. Provide a compaction test after backfill. |