Inspection Status: Partial Pass

Inspection History

Date Description Inspector Results Comments
09/16/2026 Partial Pass Send pictures of weep holes per detail before pouring. Reinforcing okay. Okay to pour pending pictures from contractor
09/25/2026 Partial Pass Okay to backfill wall. Reschedule inspection for rock pockets at weep holes.
10/01/2026 Partial Pass Retaining wall #6 okay to pour
10/07/2026 Partial Pass Retaining wall#1 dimensions and reinforcing correct. Footer okay to pour.
10/09/2026 Re-inspection required insufficient clearance to form. Chair back face prior to reinspection. Appears to be missing 2’ H=3-04 step at STA 0+00. Many verticals require trimming or splicing. Maintain 2” clearance and cover. splices are not staggered - splices shall be staggered no less than 1 splices length. 3/4” chamfer missing from top of form. Modify bottom of form to provide clearance to bent dowels.
10/13/2026 Not Ready 10/13/26 Reinforcing, weep holes, laps and layout is good but not complete. Spacing of rebar relative to forms needs to be complete. Reschedule inspection when ready.
10/14/2026 Partial Pass Issues in history have been addressed. Okay to pour pending pictures showing areas discussed with contractor..
10/15/2026 Partial Pass 1st Footer wall 5 at placida and Santiago ok to pour.
10/21/2026 Partial Pass Wall #5 Okay to pour.
10/27/2026 Partial Pass Wall waterproofed and backfill occurring. Provide a compaction test after backfill.