Inspection Status: Passed
Inspection History: Grading Progress ENGR
| Date |
Description |
Inspector |
Results |
Comments |
| 04/09/2026 |
Grading Progress ENGR |
|
Passed |
GSI basins are graded correctly, small water harvesting basin on north side is cut. Current plan on east side behind aquatics equipment building does not allow 5% slope for 10 feet away from building foundation (as required by IBC 1804.4) |
| 10/28/2025 |
Grading Progress ENGR |
|
Partial Pass |
Stormwater harvesting areas are being worked on. Middle area where old islands were is being left at original elevation. Basin floor elevations are good where finished. Recommend a perc test sooner rather than later to ensure proper infiltration. |