Parcel: 14026038C


Addresses:

5735 S TUCSON BL


Inspection Status: Partial Pass

Inspection History: For trash and recycling enclosures

Permit Number - TD-DEV-0624-00187

Inspection Description - For trash and recycling enclosures

Inspection Status - Partial Pass

Date Description Inspector Results Comments
07/31/2025 For trash and recycling enclosures Partial Pass 7/31/25
Rebar placement,spacing, #4 verts and horz are correct to Tsmr RE specifications. Footer dimensions are correct. Contractor wants to pour footer and bollards in mono pour. Bollard spacing will not be correct if poured now because bollard footings are not dug @ 3’ depth. If Contractor provides pictures illustrating bollards at correct depth and position I can Approve pour. Do not pour until approval.
08/01/2025 For trash and recycling enclosures Partial Pass Refuse enclosure footing: missing one horizontal reinforcement bar, add extra vertical reinforcement to the front edges and corners (3 total in the corners, 2 on the edges, 8in-oc). Bollards are being excluded from this pour. Correct rebar, then okay to pour.
08/11/2025 For trash and recycling enclosures Partial Pass 8/11/25
#4 verts are in place except one vert in corner is missing but it will be wet set. Bond beam at top is in place. 7 courses need to be grouted-vibrate all grouted cells and send good pictures of them vibrating ... After grout we will need to see the mat for the floor and the bollards. Call us out when ready for inspection.

3 columns at drive through are also okay to grout. 16 x 16”
#5 verts in place. #3 rings @8” oc in place.