Permit: TD-DEV-0624-00169

Parcel: 127090180


Addresses:

6105 E BROADWAY BL

Inspection Status: Not Ready

Inspection History

Date Description Inspector Results Comments
06/10/2025 Not Ready
06/20/2025 Partial Pass Bollards that provide physical separation are less than 5 ft. and fixed in footers. Retaining wall bollards are correct. All bollards placed by 6/20/25 are correct to plan. Some bollards are not installed yet.
06/27/2025 Partial Pass 6/27/25
Bollards on retaining wall are embedded a minimum 18” into concrete. Bollards need to be filled with concrete and they need finished with safety paint per PAG detail 106. All rest of bollards need to be concrete filled. Painters are due on site Monday.
07/01/2025 Passed 7/1/25 All Bollards have been filled. The remaining unpainted bollards on retaining wall are being painted per PAG 106 now.