Permit: TD-DEV-0525-00143

Parcel: 13811073C


Addresses:

6444 S FONTANA AV

Inspection Status: Not Ready

Inspection History: For trash and recycling enclosures

Date Description Inspector Results Comments
03/19/2026 For trash and recycling enclosures Not Ready 3/19/26
Footer refuse enclosure is for 16 foot wide wall. I don't see a TSMR for modifying the refuse enclosure in the plan details that shows a standard single refuge enclosure with 13'4" width. Do not pour this footer until this is result.
03/19/2026 For trash and recycling enclosures Partial Pass 3/19/26

I received Email from Any Vera Confirming the wider Refuse Enclosure is fine for recycling. Okay to pour footer after I receive pictures showing adjustments discussed with contractor -2 rebars at wall ends and no dirt within 3" of rebar
03/24/2026 For trash and recycling enclosures Partial Pass 3/24/26
Refuse Enclosure 1st lift walls grouted. Wall is finished to top course. Okay to grout to bond beam at top and finish walls.
Schedule inspection for bollard footers before pouring bollards. Schedule inspection before pouring floor. They can be poured at the same time with one inspection if it is correct if you prefer.