Permit: TD-DEV-0525-00143

Parcel: 13811073C


Addresses:

6444 S FONTANA AV

Inspection Status: Partial Pass

Inspection History

Date Description Inspector Results Comments
03/16/2026 Partial Pass North wall Footer dimensions and reinforcing correct. 2 continuous #4 rebar with alternating #4 verts at 48" OC. Contractor will build wall w/ bond beam to 1 lift at 4'. Schedule pre-grout inspection before grouting 1st lift to check reinforcing.
03/23/2026 Partial Pass 3/23/26 North Screen Wall
Bond beam in place at 1st lift. Masons duct taped bond beam at expansion joints and verts in place at 48" OC. Okay to grout 1st lift. Grout all reinforced cells and bond beam. Vibrate all grout. Schedule wall inspection for pre grout when bond beam is in place at top of wall.

Refuse Enclosure Inspection scheduled for 3/24.
Okay to Grout 1st lift of refuse enclosure. Grout all reinforced cells and bond beam at bottom and vibrate all grout. Schedule Refuse Enclosure Inspection when ready for pre grout inspection with bond beam in place at top of wall.
03/24/2026 Partial Pass 3/24/26
Bond beam is placed correct at top course. Ok to grout 2nd lift and bond beam and finish walls. Vibrate all grout.
03/26/2026 Passed