| 11/13/2026 |
|
|
Partial Pass |
4" PVC sleeves under paving/curbs is substantially all installed except for mainline where it goes under hardscape. These sleeves per plan are 2x the sum of pipes/wire diameter. If this is not the case more and/or bigger sleeves will need to be installed. Okay to backfill these sleeves as appropriate. Mainline will need to be pressure tested, when ready schedule inspection. Schedule inspection for irrigation trenching as well prior to backfilling. |