Inspection Status: Partial Pass
Inspection History: ENGR Grading Final
Permit Number - TD-DEV-0424-00110
Inspection Description - ENGR Grading Final
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2025 | ENGR Grading Final | Partial Pass | Blue top monuments are in place and level with AB. Compaction is good. Okay for pavement. | |
| 07/23/2025 | ENGR Grading Final | Failed | 07/23/25, landscape grade looks good except in 2 locations. Southwest corner and southeast corner of building. Plans show depressed areas that will create an issue with water penetration under slab conditions. Suggested to supper to top off to grade hgt of channels and then add mirafe and riprap for positive drainage. See attached pictures of both locations. | |
| 08/15/2025 | ENGR Grading Final | Failed | Aforementioned grading issues at down spouts have not been remedied. IBC 1804.4 requires positive drainage away from the building foundation. The method to achieve this is up to the contractor, but water cannot pool by the building. | |
| 08/21/2025 | ENGR Grading Final | Not Ready | 08/21/25 - Aforementioned grading issues at down spouts have not been remedied. IBC 1804.4 requires positive drainage away from the building foundation. The method to achieve this is up to the contractor, but water cannot pool by the building. | |
| 09/04/2025 | ENGR Grading Final | Passed |