| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2026 | Not Ready | 5/13/26 Handicap curb ramps and service curb ramps are correct. -The scupper at West End of parking lot under the sidewalk- The scupper plate walls were not poured with the floor. Pictures were taken to show rebar epoxied into floor to bind the floor and wall together. However pictures show that the rebar missed the walls, so that they are not connected as planned. I suggest letting it set up and drilling (Take care not to crack/break it)….through the wall and into floor and epoxying rebar through both and patch the holes. Take good pictures of this. |
||