Permit: TD-DEV-0226-00034

Parcel: 14118658A


Addresses:

10080 E OLD VAIL RD

Inspection Status: Partial Pass

Inspection History: ENGR - Drainage Structures

Date Description Inspector Results Comments
09/16/2026 ENGR - Drainage Structures Partial Pass Floor for peg 309 type four catch basin at SE corner is poured correct. Schedule inspection for when wall forms and reinforcing is ready for inspection before next pour
09/30/2026 ENGR - Drainage Structures Partial Pass
10/14/2026 ENGR - Drainage Structures Partial Pass Floor for PAG 309 double type 4 CB. Clean up around 12' at edges to reach 8" depth for floor. Okay to pour floor and wet set verts
10/15/2026 ENGR - Drainage Structures Not Ready Drainpipe inspection. 18" HDPE from double PAG 309 catch basin at far SE of site- connecting to existing 3’ drainage pipe. Engineered RFI for rerouting because of electrical line. Clean out in place correct but connection to 3 foot drain pipe is not correct to ADOT SD 13–70 it is not between 45 and 90°. Reschedule when ready
ENGR - Drainage Structures Scheduled