Permit: TC-SOL-0625-00801

Parcel: 138210670


Addresses:

220 W CORONA RD

Inspection Status: Partial Pass

Inspection History: BULD - Electrical Clearance

Date Description Inspector Results Comments
08/19/2025 BULD - Electrical Clearance Partial Pass 8/19/25
TEP CLEARANCE: INCR, called TEP @ 3:02. Partial pass pending solar.
08/22/2025 BULD - Electrical Clearance Re-inspection required 8/22/25
No response from Field contact: Chris D, phone number: (602) 790-0834. Left voicemail.
09/03/2025 BULD - Electrical Clearance Not Ready Failed per pics - 1. Unable to identify wire sizes at the different pieces of equipment, 2. PW3 inverter shall be placed over a solid surface to prevent foliage growth per installation manual
10/01/2025 BULD - Electrical Clearance Passed 10/1/25
TEP CLEARANCE: DGC/BAT