Permit: TC-RES-1224-07036

Parcel: 12006091C


Addresses:

3913 S 4TH AV

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
09/02/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9-2-26 Provide shot pins and anchor bolts at Marked locations * Trimmer to the King stud around window openings are required to be (2)16d nails 8" O.C. Was unable to walk roof due to no ladder. Truss calcs are correct. Reinspection required.
09/10/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required (with fee) 9/10/26: missing anchor bolts and nut at previously marked locations. Shot pins cannot be used on exterior walls. Add nails to loose roof panel at marked location and a ladder will be required to look at nailing for sheathing at rooftop. See previous notes regarding nailing requirements at window openings and add nails accordingly.
09/24/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 9-24-26 all previous items have been corrected. Roof has been walked OK to proceed.