Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 02/20/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
2-20-26: add nails to loose roof panel-concrete marked with an "X", provide truss calculations, add shot pins within 6" at the end of plate and 24" o.c. thereafter-minimum of 2 shot pins per plate, add anchor bolts at marked locations and a minimum of 4 anchor bolts are required for CS-WSP panels-see plans for information, add nails to sheathing at firewall and at the exterior walls at marked locations-nails shall be placed 3/8" from joints/edges. STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE NOTED. |
| 02/23/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
Approved corrections were made. No additional items were found. 2/23/2026 |