Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 7/2/25 1. All top plate penetrations are missing fire caulk. 2. Main water line needs to be supported inside. 3. Dryer vent is warped. 4. Laundry vent needs boca plates, top and sill. Top safety plate needs to extend minimum 2" below top plate. 5. Laundry is missing Electrical for dryer 6. Stud protectors needed throughout, see "x" on the studs. 7. Bathroom ABS needs boca plates; water lines need boca plates. 8. Flex line for bathroom is kinked/smashed, will need to be rerouted 9. Mortar needed at bathtub drain 10. Missing grey water line at laundry 11. Fix sharp bends in exhaust bends. |
|
| 07/03/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Not Ready | ||
| 07/03/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | Listed items were addressed, corrected and Approved. Okay to cover progress areas of unit #1 and unit #2 |