Inspection Status: Re-inspection required
Inspection History: BULD - Electrical Clearance
Permit Number - TC-RES-1123-09821
Inspection Description - BULD - Electrical Clearance
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/22/2024 | BULD - Electrical Clearance | Re-inspection required | 10/22/24: properly seal all penetrations through vapor barrier and top plate, secure gas piping on vertical and horizontal runs, all metallic boxes must be grounded, address tag missing at panel, plans call for 400amp service, sub panel requires ground busbar, gas piping must be grounded, transition glue at abs and pvc not allowed, outlet missing at guest house at kitchen wall, properly secure condensate drain. B-vent must be properly secured with 1 inch clearance from combustibles, BOCA plates required throughout at dryer vent and plumbing. Stopped inspection more items may be added | |
10/29/2024 | BULD - Electrical Clearance | Passed | Clearance for TEP ECO. 10/29/2024 |