Inspection History: COT - RSEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/29/2024 | COT - RSEL - Electrical Final | Not Ready | 2/29/24: not ready | |
| 03/07/2024 | COT - RSEL - Electrical Final | Re-inspection required | 2/29/24: not ready 3/7/24: electrical final will need to be called when project is complete. |
|
| 04/12/2024 | COT - RSEL - Electrical Final | Not Ready | ||
| 09/26/2024 | COT - RSEL - Electrical Final | Re-inspection required | 9/26/24: garage was completed before inspection need to see top plate penetrations. All Receptacles in garage need to be GFCI protected. Some receptacles call to be 48" off the ground. | |
| 10/09/2024 | COT - RSEL - Electrical Final | Re-inspection required | 10/9/24: no access | |
| 10/18/2024 | COT - RSEL - Electrical Final | Passed | 10/18/24: Penetrations are foamed, receptacles in garage are protected by a GFCI receptacle on load side. Fire restoration work is complete. Okay to close out permit. |