Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - BULD - SWG Clearance
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2024 | COT - BULD - SWG Clearance | Re-inspection required | 11/28/23 - Approved gas piping and pressure test for both units of the duplex, okay to backfill progress areas (duplex) Pending Clearance 8/6/24: water hammer arrester required at (dishwasher, refrigerator, washer), two circuits required at kitchen, receptacle spacing at kitchen countertop not meeting code requirements, Insulate and UV coat water lines, A.V.V needs to be properly installed, Arc-fault breakers missing throughout, grounding required at gas piping, no roof access, smoke detector not properly installed. |
|
| 08/12/2024 | COT - BULD - SWG Clearance | Passed | Request meter sets for units #1 and #2. | |
| 11/28/2023 | COT - BULD - SWG Clearance | Not Ready |