Permit: TC-RES-1025-05260

Parcel: 120082930

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical FinalĀ 

Date Description Inspector Results Comments
11/06/2026 COT - RSME - Mechanical FinalĀ  Re-inspection required 11/06/2026
Add 4" address number to house visible from street. Weep screed at porches to be 2" from pavement and 4" to ground perimeter of house. Label electrical panel circuits completely. Add AFCI breaker to refrigerator and kitchen circuit at unit 1. Water heater needs to be electrically connected and connect T&P drain pipe to outdoors. Add refrigerant cap to condenser at rear unit. AC breaker is over-amped on both units. Add elbow down to T&P line at hot water heater front unit. Wrap line set at air condenser. Paint all exposed plastic outdoors. Lower thermostats to 48" AFF. Provide accessible entrance per Inclusive Home Design. All outdoor lighting must project down and not out. All open conditions need to be satisfied with documents approved prior to building final.