Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2026 | COT - RSEL - Electrical Final | Not Ready | 01/07/2026 Not ready. |
|
| COT - RSEL - Electrical Final | Re-inspection required | 1-23-26:replace outdoor receptacles with bubble covers and exterior gfi's must be weather resistant (WR), arch fault breaker required for great room, add shackle at panel for mini split, mini split is not UL listed, angle exterior lights to 45 degrees or less per dark sky ordinance, breaker for mini split is under amped, exterior lights by egress door does not have a dark sky compliant housing, properly secure condensation line at west side, update panel schedule to reflect current circuits. Listing for non UL mini split can be emission tested and approved by intertek or UL-contact either for testing and certificate and submit results through portal for city review. | ||
| 02/06/2026 | COT - RSEL - Electrical Final | Passed |