Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Not Ready

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
01/07/2026 COT - RSEL - Electrical Final  Not Ready 01/07/2026
Not ready.
COT - RSEL - Electrical Final  Re-inspection required 1-23-26:replace outdoor receptacles with bubble covers and exterior gfi's must be weather resistant (WR), arch fault breaker required for great room, add shackle at panel for mini split, mini split is not UL listed, angle exterior lights to 45 degrees or less per dark sky ordinance, breaker for mini split is under amped, exterior lights by egress door does not have a dark sky compliant housing, properly secure condensation line at west side, update panel schedule to reflect current circuits. Listing for non UL mini split can be emission tested and approved by intertek or UL-contact either for testing and certificate and submit results through portal for city review.
02/06/2026 COT - RSEL - Electrical Final  Passed