Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 01/07/2026 Corrections made to 12/29/25 inspection. |
|
| 12/29/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 12-29-25: partial pass-pending 1/2" anchor bolts at several locations. Anchor bolts must be installed in the middle third of the plate; within 12" of the end of each plate & spaced no further than 6' apart. Missing 3/8" x 5" lag bolts at each connection-see ledger detail for more. This items will be checked at intermediates-okay to dry-in roof and continue with construction without covering the mentioned listed items. |