Permit: TC-RES-1025-04835

Parcel: 138041240


Addresses:

934 W CALLE MEDINA

Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
10/26/2026 COT - RSEL - Electrical Final  Re-inspection required 10-26-26 High waterloop under kitchen sink going to dishwasher should be mounted at its highest point* hammer arrestor missing at hot water going to dishwasher* provide hammer arresters at washing machine inlet* window at shower in master bathroom is required to be tamper glass, provide specs for proof* All exterior receptacles are to be GFCI protected as well as WR approved* correctly fasten electrical box on back porch-right of electrical panel at North west corner* Provide tall enough ladder for roof access to properly inspect condensing unit* reinspection is required at this time. More items may be added
10/28/2026 COT - RSEL - Electrical Final  Passed 10/28/2026
All corrections made. Verified roof mechanical equipment.