Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 9.2.2025 Secure water and ABS pipes midway and add Boca plates, firefoam the top plates throughout, smoke alarms missing in bedroom and main room, secure electrical lines near panel, missing receptacle at kitchen counter, receptacles need to be made up in box, missing mechanical equipment. Missing anchor bolts every 48" OC & within 12" of edge on west bearing wall, shot pins required 6" from edge and 2x for greater than 12" and every 32" on center per plan. |
|
| 11/20/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 11.20.2025 All corrections made to prior inspection. Added fire foam to top plate penetrations, braced register ducts, shower tested for leaks, lowered thermostat to 48", ensured receptacle spacing at kitchen counter top. Okay to proceed with construction. |