Permit: TC-RES-1024-05976

Parcel: 137054440


Addresses:

766 W NEBRASKA ST

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
09/02/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9.2.2025
Secure water and ABS pipes midway and add Boca plates, firefoam the top plates throughout, smoke alarms missing in bedroom and main room, secure electrical lines near panel, missing receptacle at kitchen counter, receptacles need to be made up in box, missing mechanical equipment. Missing anchor bolts every 48" OC & within 12" of edge on west bearing wall, shot pins required 6" from edge and 2x for greater than 12" and every 32" on center per plan.
11/20/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 11.20.2025
All corrections made to prior inspection. Added fire foam to top plate penetrations, braced register ducts, shower tested for leaks, lowered thermostat to 48", ensured receptacle spacing at kitchen counter top. Okay to proceed with construction.