Inspection History Details
Inspection Status: Partial Pass
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2024 | RSBU - Building Final | Partial Pass | ||
| 06/05/2024 | RSBU - Building Final | Re-inspection required | Install stove and cabinets, open crawl space access to 30 x22 Gfi required for washing machine, smoke detectors are not working properly 6/5/24: water heater missing sediment trap, b-vent requires 1" clearance from combustibles, WR receptacles missing at outdoor receptacles, properly secure whip at ac unit, arc fault breaker's missing throughout, |
|
| 06/06/2024 | RSBU - Building Final | Re-inspection required | Gfi required for washing machine, smoke detectors are not working properly 6/5/24: water heater missing sediment trap, b-vent requires 1" clearance from combustibles, WR receptacles missing at outdoor receptacles, properly secure whip at ac unit, arc fault breaker's missing throughout, 6/6/24: circuits at panel cannot double tap on a single pole breaker. Revision will be needed to add new panel or sub-panel. |
|
| 06/20/2024 | RSBU - Building Final | Passed | Gfi required for washing machine, smoke detectors are not working properly 6/5/24: water heater missing sediment trap, b-vent requires 1" clearance from combustibles, WR receptacles missing at outdoor receptacles, properly secure whip at ac unit, arc fault breaker's missing throughout, 6/6/24: circuits at panel cannot double tap on a single pole breaker. Revision will be needed to add new panel or sub-panel. 6/20/24: corrections made |