Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
05/08/2026 COT - RSME - Mechanical Final  Not Ready Not ready. None of the following issues have been addressed from the last inspections. 5/8/2026
05/13/2026 COT - RSME - Mechanical Final  Not Ready 5/13/2026
Not ready. See prior inspection notes.
10/15/2025 COT - RSME - Mechanical Final  Not Ready
12/02/2025 COT - RSME - Mechanical Final  Not Ready Home owner refused for unit inspection. Call back in when customer is ready. 12/2/2025
12/10/2025 COT - RSME - Mechanical Final  Re-inspection required junior flex does not have a sun shield that is close enough to do its job to the junior flex. Unit appears to have a leak underneath the unit. The stand supporting the unit should not be located on the eve of the roof and. If no heat strips are installed please mark it in the appropriate spot on the data tag.


12/10/25
1. The unit is missing screws on some of the panels.
2. Condensation line needs to be painted to prevent sun damage
3. Duct transition is torn and not sealed properly underneath.
4. There is a T-stat wire in the control cabinet that is exposed and should be capped.
5. Double check the placement of Unit stand appears to be too close to Eve; have a structural engineer approve the location.
6. Annotate appropriate check box on data plate for heat strips.
7. Attach both liquid tight lines to red wood and keep off roof membrane.