Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 3/12/26:Revision required for changes made to framing members( plans call for 2x6 exterior walls), 2x solid blocking required at roof, exterior sheathing missing nailing throughout (6"/12" required), anchor bolts must be spaced no more than 6" o.c and shall be no more than 12" from edge and no less than 3.5" from edge (must be installed in middle third of sill plate). Weep screed shall be 2" above concrete landing at entry and landing shall be corrected. | |
| 07/07/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 07/07/2026 Corrections made to prior inspection, footing was verified and revision submitted. |