Permit: TC-RES-0924-05251

Parcel: 126151290


Addresses:

4411 E TIMROD ST

Inspection Status: Re-inspection required

Inspection History: BULD - Electrical Clearance

Date Description Inspector Results Comments
02/20/2025 BULD - Electrical Clearance Re-inspection required 1-Grounding electrode conductor must be continuous to first electrode.
2-Provide second ground rod, or testing to verify maximum resistance per Code.
3-Connections to ground rods must be accessible.
02/28/2025 BULD - Electrical Clearance Passed INCR
05/23/2025 BULD - Electrical Clearance Re-inspection required 5/23/25
1. Loose outlet in Master bedroom
2.caulk need on toilet
3. Kitchen small appliance is on 1 circuit
4. Island has no power.
5. Water hammer arrestors needed at ice maker and dishwasher, washer.
6. GFCI needed for washer.
7. Dishwasher/garbage disposal needs to be GFCI protected.
05/28/2025 BULD - Electrical Clearance Passed 5/28/25
Pass