Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 08/04/2025 |
RSBU - Building Final |
|
Re-inspection required |
Provide address at home. Receptacles in laundry room tied into lighting and exhaust. Provide a second opening to outdoor in water heater closet. Kitchen receptacles tied into lighting circuits. Missing receptacles at kitchen island. Provide hammer arrestors for dishwasher and refrigerator. Install dishwasher at time of inspection. Provide a cooking appliance prior to final. Master bathroom receptacles tied into lighting circuits. Caulk tub. Hall bathroom has same issues. Missing receptacles for double lav. Panel not per schedule. Provide arc fault breakers at all living spaces. Provide WR receptacles for outdoors. Romex not rated for outdoor use. Provide treaded wood and coated schedule 40 pvc for condensation line. Provide a KO seal at disconnect box. 8/4/2025 |
| 08/12/2025 |
RSBU - Building Final |
|
Passed |
|