Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 6/30/25: Seal all penetrations through top plates and vapor barrier, nail plates required at bedroom #2 and laundry room, properly support pex line in ceiling at bedroom #1, properly support gas line at ceiling in bedroom #1, smoke detector required outside bedrooms, fire blocking required at soffit areas at laundry room, seal penetration from existing home into addition in soffit areas. Damaged sheathing at NM cable at sub panel must be taped. Lath passed. | |
| 07/03/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 7/3/25 pass |