Permit: TC-RES-0824-04666

Parcel: 134242240


Addresses:

802 S FORDHAM DR

Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
02/19/2025 COT - RSEL - Electrical Final  Re-inspection required no access for inspection.
COT - RSEL - Electrical Final  Re-inspection required 2-20-25, revisions for mini splits under review, install missing covers on receptacles in laundry room, install 2 receptacles in guest room-receptacles are required within 6 ft. of a door opening and another no more than 12ft apart., minimum of 2 circuits required for kitchen. For gas reconnect, a 15 pound gauge is required and must pressurized to 15psi. Provide a 1 inch clearance on water heater B vent.
03/06/2025 COT - RSEL - Electrical Final  Not Ready No approved plans on site.
03/25/2025 COT - RSEL - Electrical Final  Passed