Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2025 |
COT - RSEL - Electrical Final |
|
Re-inspection required |
no access for inspection. |
|
COT - RSEL - Electrical Final |
|
Re-inspection required |
2-20-25, revisions for mini splits under review, install missing covers on receptacles in laundry room, install 2 receptacles in guest room-receptacles are required within 6 ft. of a door opening and another no more than 12ft apart., minimum of 2 circuits required for kitchen. For gas reconnect, a 15 pound gauge is required and must pressurized to 15psi. Provide a 1 inch clearance on water heater B vent. |
| 03/06/2025 |
COT - RSEL - Electrical Final |
|
Not Ready |
No approved plans on site. |
| 03/25/2025 |
COT - RSEL - Electrical Final |
|
Passed |
|