Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 04/24/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
1-Front wall has been stacked, creating a “hinge”; provide engineering to verify its adequacy. 2-All rafters are missing bird’s mouths. 3-Siding must be nailed at 4” and 8” pattern to be used as bracing. 4-East wall sole plate has been stacked, without sheer tying to bottom-most plate; provide strapping at 32” OC to tie the two plates together. |
| 05/01/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Partial Pass |
Partial pass, contractor had questions on how to fix previous issues |
| 05/12/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|