Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof NailingĀ 

Date Description Inspector Results Comments
10/29/2026 COT - RSBU - Roof NailingĀ  Re-inspection required 1. About 75% of the sheating has been rained on and are delaminating or have lost structural integrity and over driven nails have added insult to injury.
2. Nails driven to close to edges of panels and have caused edge blow or splitting on some rafters. Should be 3/8" minimum from edges
3. Over driven nails on majority of sheating crushing wood fibers. Nails should sit flush with sheating or no more than 1/16".
4. Remove and replace damaged sheathing; correct sheating spacing, add properly coated ring shank roof nails.