Inspection History Details
Inspection Status: Not Ready
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2026 | RSBU - Building Final | Not Ready | ||
| 09/17/2026 | RSBU - Building Final | Re-inspection required | Please call after power is restored 09/17/2026 AC breaker is over-amped, requires a max 30A fuse. Paint exposed plastic vent pipes. Add smoke detector to bedroom. Secure AC electrical whip to wall. Add AFCI breakers to all habitable rooms, hallway, kitchen and living room area circuits at main panel and label all breakers. Laundry room receptacle needs to be GFCI. |
|
| 09/22/2026 | RSBU - Building Final | Partial Pass | 09/22/2026 All conditions need to be satisfied. All items have been corrected. |
|
| 09/24/2026 | RSBU - Building Final | Passed | 09/24/2026 Uploaded truss calcs/design to satisfy remaining open condition - see attachment. |