Permit: TC-RES-0725-03718

Parcel: 117020120

Inspection Status: Not Ready

Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
08/24/2026 RSBU - Building Final  Not Ready
09/17/2026 RSBU - Building Final  Re-inspection required Please call after power is restored


09/17/2026
AC breaker is over-amped, requires a max 30A fuse. Paint exposed plastic vent pipes. Add smoke detector to bedroom. Secure AC electrical whip to wall. Add AFCI breakers to all habitable rooms, hallway, kitchen and living room area circuits at main panel and label all breakers. Laundry room receptacle needs to be GFCI.
09/22/2026 RSBU - Building Final  Partial Pass 09/22/2026
All conditions need to be satisfied. All items have been corrected.
09/24/2026 RSBU - Building Final  Passed 09/24/2026
Uploaded truss calcs/design to satisfy remaining open condition - see attachment.