Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2025 | COT - RSPL - Plumbing Final | Re-inspection required | 7.15.25 Pex support missing throughout. Vertical runs must be supported every 48" and horizontal runs must be supported every 32". Water line leaking at toilet. Stud over notched at primary bedroom. Shoe or sister stud required. Excavated run to meter requires inspection BEFORE backfill. Open trench in 3 areas (2'x2'x depth of pipe) at beginning, middle, and end so inspector and confirm proper depth throughout. Hammer arrester missing at washer in kitchen. |
|
| 07/16/2025 | COT - RSPL - Plumbing Final | Passed |