Permit: TC-RES-0724-04251

Parcel: 136382310


Addresses:

4757 S GOLDENROD PL

Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
02/06/2025 RSBU - Building Final  Re-inspection required 2-6-25, not ready for final inspection-install vacuum breakers on hose bibs, install stove and dishwasher, missing fixtures to include: sinks & water closet, seal additional water closet, missing water heater, breakers at panel not labeled together with missing metallic address label for panel, light bulbs not installed on exterior light fixtures, panel not energized.
06/27/2025 RSBU - Building Final  Re-inspection required 6/27/25
1. Water hammer arrestor needed for dishwasher, dishwasher not secured
2. GFCI circuit in kitchen not working
3. Garbage disposal/dishwasher receptacle not working
4. Bedroom 3: receptacles have open hot.
5. Bedroom 2: smoke detector needs to be minimum 3 ft from supply register.
6. Thermostat too high, no higher than 48".
7. Laundry receptacle needs to be GFCI protected.
8. Need condensate line for hvac, and must be painted.
9. Run t/p to safer location.
10. Need Carbon Monoxide detector.
07/15/2025 RSBU - Building Final  Passed 7/15/25 passed